| CAPACITY |
3000VA |
|
| LOAD CAPACITY |
3000W / 2700W / 2400W |
|
| INPUT VOLTAGE |
NOMINAL VOLTAGE: 200/208/220/230/240VAC
INPUT VOLTAGE RANGE: 110-280 VAC (BASED ON LOAD AT 50%)
FREQUENCY RANGE: 46HZ-54HZ / 56HZ-64HZ
PHASE: SINGLE PHASE WITH GROUND
POWER FACTOR: R0.99 @ NOMINAL VOLTAGE (100% LOAD) |
|
| OUTPUT VOLTAGE |
OUTPUT VOLTAGE: 200/208/220/230/240VAC
VOLTAGE REGULATION: ±1%
FREQUENCY RANGE (SYNCHRONIZED RANGE): 46 ~ 54 HZ OR 56 ~ 64 HZ
FREQUENCY RANGE (BATT. MODE): 50 HZ OR 60 HZ ±0.1%
CURRENT CREST RATIO: 3:01 |
|
| BATTERY |
BATTERY TYPE: 12 V / 8.2AH
NUMBERS: 6
TYPICAL RECHARGE TIME: 4 HOURS RECOVERY TO 90% CAPACITY
CHARGING CURRENT (MAX.): 1.0A
DC VOLTAGE: 72 VDC |
|
| ALARM |
BATTERY MODE: SOUNDING EVERY 4 SECONDS
LOW BATTERY: SOUNDING EVERY SECOND
OVERLOAD: SOUNDING TWICE EVERY SECOND
FAULT: CONTINUOUSLY SOUNDING |
|
| INDICATIONS |
LED PANEL: UPS STATUS, LOAD LEVEL, BATTERY LEVEL, INPUT/OUTPUT VOLTAGE, AND FAULT CONDITIONS |
|